HEAD START CENTER DESIGN GUIDE
Table
of Contents | Chapter: 1
| 2 | 3 | 4
| 5 | 6 | 7
| 8 | 9 | 10
| Appendix: A | B
| C | D | Selected
References
Chapter 10: Technical Criteria
Sections: 10.1
| 10.2 | 10.3 |
10.4 | 10.5 | 10.6
| 10.7 | 10.8 |
10.9 | 10.10 |
10.11
This chapter provides suggested technical criteria for the design and
construction of elements and systems in a center. Refer to 45 CFR 1304.53(a)
and (b) for pertinent Head Start Performance Standards.
10.1 Safety
GSA advises that center design and location are of the utmost importance
to safety. Safety is a fundamental planning consideration, involving security,
design, agency, and operations stakeholders. The following applicable
requirements are in the most recent edition of the National Fire Protection
Association (NFPA), Standard No. 101, Life Safety Code, as modified:
- Mount panic hardware on egress doors a maximum of 3 ft. above the
finished floor.
- Provide both audible and visual fire alarm signals. In addition to
fire alarms that sound in the center itself, any fire event should be
annunciated on the central building panel or a 24-hour manned security
post. See the most current editions of NFPA 72 Chapter 5 and UL 1971
for requirements on audible and visible alarms.
- Every effort shall be made to locate the entire center on the ground
level (level of exit egress) either along an outside wall with window
access to the exterior, or along a courtyard with window access. Centers
adjacent to a courtyard should have approved fire egress out of the
courtyard itself to an area of safety. If portions of the center are
located on the floor above the level of exit egress, only pre-school
children should be housed there. In no instance shall any portion of
the center be located higher in the building more than the floor above
the level of egress. The center should not be located below a level
of egress, unless the entire building is fitted for sprinklers and the
arrangement is approved by the local fire authority. All arrangements
should ensure safe egress in the event of fire. The center should have
at least one door leading directly to the outside. Each center should
have at least two means of egress with exits via protected corridors
including the required fire separations. There should be two means of
egress for each floor. State and local requirements will affect this
design.
- It would be advisable to separate Head Start centers from other occupancies,
depending on the fire gradient of the adjacent occupancy. In no case
should the separation be less than a minimum of a one-hour fire-resistant-rated
wall with doors with a fire protection rating of not less than 20 minutes.
A fire detection, alarm, and communications system should be installed
in all centers that meet the requirements of the NFPA Standards No.
70, NEC, NFPA 72, Standard for the Installation, Maintenance, and Use
of Protective Signaling Systems, NFPA 72E, Standard on Automatic Fire
Detector. The design should comply with local and state fire safety
requirements. In the event of conflict, the more stringent requirements
should apply.
- Adjacent hazardous areas, e.g., a boiler room without sprinklers,
shall be separated from the center by a minimum two-hour fire-resistant-rated
wall with self-closing doors with a fire protection rating of not less
than 90 minutes.
- Adjacent hazardous areas, e.g., a boiler room with sprinklers should
be separated from the center by a minimum one-hour fire-resistant-rated
wall with self-closing doors with a fire protection rating of not less
than 45 minutes.
- The center should be protected by an approved supervised automatic
system using quick-response sprinkler heads throughout. In areas such
as multipurpose rooms where there may be ball throwing activities, for
instance, sprinklers should have guards.
- The sleeping and napping areas of the center should be protected
by an approved supervised smoke detection system. Smoke detectors should
be installed in all areas of the center, especially in unoccupied areas,
including closets and closed space. This provision enhances flexibility,
since it allows the location of sleeping and napping areas that require
smoke detection to be changed in the future.
- Dead-end corridors should not exceed 20 ft. Travel distance within
any room in the center to a door leading to a means of egress should
not exceed 50 ft., and travel distance from that point to an exit should
not exceed 98 ft.
- It is advisable to test all existing painted surfaces in the interior
of the center for lead-based paint and to follow Department of Housing
and Urban Development (HUD) guidelines. In addition, exterior paint
in an area that children may access should be tested. All lead-based
paint detected should be abated using HUD procedures and retested to
ensure compliance. Refer to Lead-Based Paint: Interim Guidelines for
Hazard Identification and Abatement in Public and Indian Housing, 1990
(HUD).
- For new and major renovations that involve plumbing, it is advisable
to test all sources of water used by the center for lead at the acceptance
of the substantially completed project. Buildings over 25 years old
should be tested annually, at a minimum using guidance in the Environmental
Protection Agency pamphlet Lead in School's Drinking Water, EPA 570/9-89-001,
January 1989. If the lead levels exceed 20 parts per billion, the affected
water supply should not be used and mitigation actions should be taken.
- The center or the area anticipated to house the center should be
surveyed for the presence of asbestos-containing materials. Any asbestos-containing
materials that are damaged or subject to disturbance should be abated
in accordance with regulatory requirements and guidelines. In a limited
area of the country, typically with highly acidic drinking water, water
may also contain asbestos. Although this is considered less hazardous
than friable asbestos found in buildings, the drinking water supply
should be tested for the presence of asbestos and means taken to eliminate
it, if it poses a hazard. (See Raising Children Toxic Free by Needleman
and Landrigan, referenced in the "Selected References" section of the
guide.)
- It is advisable to test the center for radon in the air using alpha
track detectors or electric ion chambers for a minimum of 90 days. If
radon levels are at, or exceed, 4 picoCuries per liter, mitigation actions
should be taken. Allow a new center to "air out" before occupancy. GSA
recommends that the schedule of work provide ventilation for off-gassing
of new synthetic materials for 30 days.
- If the drinking water used by the center is obtained from a non-public
water source, test the center for radon in water. Environmental Protection
Agency guidelines should be used for testing as prescribed in Radon
in Water Sampling Manual (EPA/EERF-Manual-78-1). If radon levels are
at, or exceed, 300 picoCuries per liter, the affected water supply should
not be used and mitigation actions should be taken followed by retesting.
- When screened operable windows are used, guards should be installed
to protect children from falling through the screens.
- There should not be any sharp edges within children's areas. All
corners on trim, counters, partitions, and shelving should have rounded
edges with a 1/2 inch minimum radius. In areas accessible to children,
there should not be any openings between 3.5 and 9 inches to prevent
head entrapment.
- Interior glass should not present a safety risk for children and
should comply with code. Only glass that will not break in close proximity
to children's activities, or will not harm children or puncture skin
when glass is broken, should be used.
- Locked storage for medications and dangerous products should be provided.
Additionally, childproof interior hardware devices should be mounted
on the interior of cabinets that are within children's reach.

Copyright © 2001-2006 Trans-Management Systems
Corporation. All rights reserved.
Please Note: Links on this site are verified monthly.
While links are evaluated before being included on this site, HSIPC is not responsible for the information presented on external sites.
Last Modified: 5/30/02